Electrical supply, Korea
Contents

C4 EB/ES

C4 EB/ES

 

 

20.10

20.20

3~ 220 V 60 Hz (3/PE)

 

 

Rated power consumption

[kW]

35.3

61.1

Convection power

[kW]

34.4

60.1

Steam power (EB only)

[kW]

24.6

36.3

Rated current

[A]

92.6

160.3

Fuse rating

[A]

100

160

Residual current

[mA]

-

-

Protective earth current

[mA]

-

-

Recommended conductor cross-section for wires laid uncovered in air up to 5 m in length.

[mm2]

4G35

4G70

Residual-current device

Type

A/B

A/B

3N~ 380V 60Hz (3/N/PE)

 

 

Rated power consumption

[kW]

35.1

60.7

Convection power

[kW]

34.4

60.1

Steam power (EB only)

[kW]

24.6

36.3

Rated current

[A]

53.3

92.2

Fuse rating

[A]

63

100

Residual current

[mA]

~16.5

~16.5

Protective earth current

[mA]

~16.5

~16.5

Recommended conductor cross-section for wires laid uncovered in air up to 5 m in length.

[mm2]

5G16

5G35

Residual-current device

Type

A/B

A/B


Up